Solutions for Protecting andManaging the Electrical Network
NP800 SERIES
New generation protection relays
Our know-how in the domain of electrical network protection by static and numerical relays has led to the development of new generations of products that comply with the most demanding quality standards and the most recent technological concepts. One of the results of this expertise is
the numerical NP800 relay range.
The NP800 relays provide the protection of people, networks and electric installations and they allow communication with SCADA systems. As well as the usual protection functions of former ranges, the multifunctional NP800 relays provide monitoring, measurement and recording of the network electrical quantities.
Common characteristics for the NP800 range:
- Auxiliary supply ranges: 19V to 70V or 85V to 255V (AC or DC)
- 2 setting tables
- Self-diagnosis: RAM, ROM, EEPROM, output relays, A/D converters, auxiliary supply, monitoring of software execution time
- Optional I/O extension board (included when directional function is present)
- Setting, reading, measuring and recording are all available locally or remotely
- Complies with IEC 60255-4 standard.
- Monitoring of circuit breaker failure
- Event recording: 250 events, 10ms resolution
- 4 disturbance recordings in COMTRADE format
CONFIGURATION SOFTWARE
SMARTsoft | Configuration software for NP.800 range relays |
DEVICE LIST
Dispositivo | ANSI | Descrizione | |
---|---|---|---|
NPG800 | 21, 24, 27, 32, 37, 40, 46, 49, 50, 51, 50V, 51V, 59, 59N, 64, 81, 50BF, 74TC, 86 | Multi function generator protection | |
NPI800 | 46, 46BC, 49, 50, 50N, 50BF, 51, 51N, 86, 74TC | Phase and Earth Overcurrent Protection | |
NPID800 | 46, 46BC, 49, 50, 50N, 50BF, 51, 51N, 67, 67N, 86, 74TC | Phase and Earth Overcurrent Protection with directional criteria | |
NPIH800 | 50N, 50NBF, 51N, 86, 74TC | Earth Overcurrent Relay | |
NPIHD800 | 50N, 50NBF, 51N, 67N, 86, 74TC | Earth Overcurrent Relay with directional criteria | |
NPU800 | 27, 27P, 47, 59, 59N, 74TC, 81, 86 | Voltage and Frequency Relay | |
NPUH800 | 59N, 86, 74TC | Residual Overvoltage Relay (Neutral Displacement Relay) | |
NPM800 | 37I, 46, 48, 49, 5/49, 50, 50BF, 51LR, 51N, 66, 86, 74TC | Multi function motor protection | |
NPRG810-1G NPRG810-4G |
25, step up transformer adaptation | Generator Synchro-check relay | |
NPRG860 NPRG870 |
25, 90, step up transformer adaptation | Automatic synchronizer device for up to 4 generators | |
NPSC800-1 NPSC800-2 |
25 25 + network managment |
Network Check Synchronizing Relay | |
NPW800 | 32, 37, 27, 59, 59N, 55, 81, 86, 74TC, BF | Multi function power, voltage and frequency protection |
downloads
Document | Lang. | Ref. | Index | |
---|---|---|---|---|
General presentation NP800 & NP800R Series | EN | A449 | F | |
Application Guide NP800 & NP800R Series | EN | A331 | J | |
Fixing and Dimensions NP800 | EN / FR | D37739 | H |