Solutions   for   Protecting   andManaging   the   Electrical   Network

IAG   7014 / 7034

High impedance differential protection

The IAG 7014 and IAG 7034 relays provide high speed protection which is stable and, at the same time sensitive, at a cost considerably lower than biased differential protection.
The IAG 7014 and IAG 7034 relays may be used in the following circumstances:

  • Instantaneous longitudinal differential protection of bus-bars and eventually alternators, synchronous or induction machines (IAG 7034).
  • Instantaneous restricted earth fault protection of bus-bars or transformers (IAG 7014).
  • Instantaneous transverse protection of machines with two windings in parallel.

Their modular draw-out case, type R, may be mounted either as a separate relay, flush or projection mounting, or as an alement in a standard 19" rack cradle.

PROTECTION   FUNCTIONS

  • High impedance differential protection [87]

MAIN   FEATURES

  • Nominal current: 1 or 5 A
  • Nominal frequency: 50 or 60 Hz
  • 3 Setting Range available: 5-20%, 10-40% and 20-80%
  • Tripping time: 0,030 sec
  • 2 output contacts
  • Hand Reset mechanical opearation indicator

downloads

  Device Doc. Type Lang. Ref. Index
IAG 7014 / 7034 Leaflet EN / FR FA862 A
IAG 7014 / 7034 User Manual EN M.1731 B
IAG 7014 Connection/Definition Diagram EN / FR 9689 B
IAG 7034 Connection/Definition Diagram EN / FR 9671 I